Operating instructions
Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
499
Table 12- 13 Version A, 500 V – 690 V 3 AC, part 2
Order number 6SL3710 7LG31-5AA0 7LG31-8AA0 7LG32-2AA0
Unit rating
- for I
L
at 50 Hz 690 V
1)
- for I
H
at 50 Hz 690 V
1)
- for I
L
at 50 Hz 500 V
1)
- for I
H
at 50 Hz 500 V
1)
- for I
L
at 60 Hz 575 V
2)
- for I
H
at 60 Hz 575 V
2)
kW
kW
kW
kW
hp
hp
132
110
90
90
150
125
160
132
110
90
150
150
200
160
132
110
200
200
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
150
142
134
213
175
170
157
255
215
208
192
312
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
144
210
166
253
202
308
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Internal
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
500 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 5.75 11.02 11.44
Cooling air requirement m
3
/s 0.58 1.19 1.19
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 71/73 75/77 75/77
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
95
4 x 240
M12 (2 holes)
120
4 x 240
M12 (2 holes)
2 x 70
4 x 240
M12 (2 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
95
2 x 150
M12 (2 holes)
120
2 x 150
M12 (2 holes)
2 x 70
2 x 150
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
300 / 450
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
1400
2000
600
1600
2000
600
1600
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
FI
FX
FX
GI
GX
GX
GI
GX
GX
Weight (without options), approx. kg 708 892 892