12.3.2 Cabinet unit version A, 500 V - 690 V 3 AC
Table 12- 12 Version A, 500 V – 690 V 3 AC, part 1
Order number 6SL3710 7LG28-5AA0 7LG31-0AA0 7LG31-2AA0
Unit rating
- for I
L
at 50 Hz 690 V
1)
- for I
H
at 50 Hz 690 V
1)
- for I
L
at 50 Hz 500 V
1)
- for I
H
at 50 Hz 500 V
1)
- for I
L
at 60 Hz 575 V
2)
- for I
H
at 60 Hz 575 V
2)
kW
kW
kW
kW
hp
hp
75
55
55
45
75
75
90
75
55
55
75
75
110
90
75
75
100
100
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
85
80
76
120
100
95
89
142
120
115
107
172
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
86
125
99
144
117
170
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Internal
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
500 V 3 AC -10 % to 690 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 5.12 5.38 5.84
Cooling air requirement m
3
/s 0.58 0.58 0.58
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 71/73 71/73 71/73
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
50
4 x 240
M12 (2 holes)
50
4 x 240
M12 (2 holes)
70
4 x 240
M12 (2 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
50
2 x 70
M12 (2 holes)
50
2 x 150
M12 (2 holes)
70
2 x 150
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
300 / 450
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
1400
2000
600
1400
2000
600
1400
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
FI
FX
FX
FI
FX
FX
FI
FX
FX
Weight (without options), approx. kg 708 708 708