Operating instructions
Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
495
Table 12- 11 Version A, 380 V – 480 V 3 AC, part 4
Order number 6SL3710 7LE41-2AA0 7LE41-4AA0
Unit rating
- for I
L
at 50 Hz 400 V
1)
- for I
H
at 50 Hz 400 V
1)
- for I
L
at 60 Hz 460 V
2)
- for I
H
at 60 Hz 460 V
2)
kW
kW
hp
hp
710
560
1000
900
800
710
1000
1000
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
1260
1230
1127
1845
1405
1370
1257
2055
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
1133
1891
1262
2107
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
380 V 3 AC -10 % to 480 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 33.05 33.95
Cooling air requirement m
3
/s 2.6 2.6
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 78/80 78/80
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
4 x 240
8 x 240
M12 (4 holes)
6 x 185
8 x 240
M12 (4 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
4 x 240
6 x 240
M12 (3 holes)
6 x 185
6 x 240
M12 (3 holes)
Protective conductor connection
Fixing screw
M12 (18 holes)
M12 (18 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
2800
2000
600
2800
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
JI
JX
JX
JI
JX
JX
Weight (without options), approx. kg 2408 2408