Operating instructions
Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
489
12.3.1 Cabinet unit version A, 380 V - 480 V 3 AC
Table 12- 8 Version A, 380 V – 480 V 3 AC, part 1
Order number 6SL3710 7LE32-1AA0 7LE32-6AA0 7LE33-1AA0
Unit rating
- for I
L
at 50 Hz 400 V
1)
- for I
H
at 50 Hz 400 V
1)
- for I
L
at 60 Hz 460 V
2)
- for I
H
at 60 Hz 460 V
2)
kW
kW
hp
hp
110
90
150
150
132
110
200
200
160
132
250
200
Output current
- Rated current I
N A
3)
- Base load current I
L
4)
- Base load current I
H
5)
- Max. current I
max A
A
A
A
A
210
205
178
307
260
250
233
375
310
302
277
453
Infeed/regenerative current
- Rated current I
N E
6)
- Maximum current I
max E
A
A
197
315
242
390
286
467
Max. current requirement
- Auxiliary 24 V DC supply
A
Internal
Internal
Internal
Connection voltages
- Line voltage
- Line frequency
- Electronics power supply
V
ACrms
Hz
V
DC
380 V 3 AC -10 % to 480 V 3 AC +10 % (-15 % < 1 min)
47 to 63 Hz
24 (20.4 - 28.8)
Power loss kW 6.31 7.55 10.01
Cooling air requirement m
3
/s 0.58 0.70 1.19
Sound pressure level L
pA
(1 m) at 50/60 Hz
dB(A) 71/73 71/73 72/74
Line connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
2 x 70
4 x 240
M12 (2 holes)
2 x 95
4 x 240
M12 (2 holes)
2 x 120
4 x 240
M12 (2 holes)
Motor connection
- recommended: DIN VDE
7)
- maximum: DIN VDE
- Fixing screw
mm
2
mm
2
2 x 70
2 x 150
M12 (2 holes)
2 x 95
2 x 150
M12 (2 holes)
2 x 120
2 x 150
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Max. motor cable length
shielded / unshielded
m
300 / 450
300 / 450
300 / 450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
1400
2000
600
1400
2000
600
1600
2000
600
Frame sizes
- Active Interface Module
- Active Line Module
- Motor Module
FI
FX
FX
FI
FX
FX
GI
GX
GX
Weight (without options), approx. kg 708 708 892