12.2 General technical specifications
Drive converter cabinet units
482 Operating Instructions, 10/2008, A5E00288214A
12.2 General technical specifications
Table 12- 1 General technical specifications
Electrical data
Line system configurations TN/TT supplies or insulated supplies (IT supplies)
Line frequency 47 Hz to 63 Hz
Output frequency 0 Hz to 300 Hz
Power factor Variable via reactive current (factory setting: cos φ = 1)
Switching at input Once every 3 minutes
Mechanical data
Degree of protection IP20 (higher degrees of protection up to IP54 optional)
Class of protection I to EN 50178, Part 1
Cooling method Forced air cooling AF to EN 60146
Sound pressure level L
pA
(1 m) ≤ 78 dB(A) at 50 Hz line frequency
≤ 80 dB(A) at 60 Hz line frequency
Touch protection BGV A3
Cabinet system Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
Paint finish RAL 7035 (indoor requirements)
Compliance with standards
Standards EN 60146-1, EN 61800-2, EN 61800-3, EN 50178
1)
, EN 60204-1, EN 60529
2)
CE mark To EMC directive No. 2004/108/EC and low-voltage directive No. 2006/95/EC
RI suppression In accordance with the EMC product standard for variable-speed drives EN 61800-3,
"second environment".
Application in "first environment" possible with line filters (option L00).
Ambient conditions Storage Transport During operation
Ambient temperature -25 ... +55 °C -25 ... +70°C
as of
–40 °C
for 24 hours
0
... +40 °C
up to +50 °C with derating
Humidity range
2)
(non-condensing)
corresponds to class
5 to 95 %
1K4 to EN 60721-3-1
5 ... 95 % at 40 °C
2K3 to EN 60721-3-2
5 ...
95 %
3K3 to EN 60721-3-3
Environmental class/harmful
chemical substances
2)
1C2 to EN 60721-3-1 2C2 to EN 60721-3-2 3C2 to EN 60721-3-3
Organic/biological influences
2)
1B1 to EN 60721-3-1 2B1 to EN 60721-3-2 3B1 to EN 60721-3-3
Installation altitude Up to 2000 m above sea level without derating,
> 2000 m above sea level with derating (see "Derating data")