Electrical installation
4.2 Checklist for electrical installation
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
45
Item Activity Fulfilled/Complete
8 The type plate can be used to ascertain the date of manufacture. If the period from the
date of manufacture to initial commissioning or the cabinet unit downtime is less than two
years, the DC link capacitors do not have to be re-formed. If the downtime period is longer
than two years, they must be reformed in accordance with the description found in the
section "Maintenance and servicing / Reforming the DC link capacitors".
9 With an external auxiliary supply, the cable for the 230 V AC supply must be connected to
terminal -X40 (see "Electrical installation / Power connections / External supply of the
auxiliary supply from a secure line").
10 Option L10
dv/dt filter plus
Voltage Peak
Limiter
During commissioning, the filter must be selected via STARTER or
AOP30. You are advised to check the selection by ensuring that
p0230 is set to 2.
The required parameters are set automatically (see "Electrical
installation / Other connections / dv/dt filter plus Voltage Peak Limiter
(option L10)").
11 Option L15
Sine-wave filter
During commissioning, the filter must be selected via STARTER or
AOP30. You are advised to check the selection by ensuring that
p0230 is set to 3.
The required parameters are set automatically (see "Electrical
installation / Other connections / Sine-wave filter (option L15)").
12 Option L19
Connection for
external auxiliary
equipment
To supply auxiliary equipment (e.g. separately-driven fan for motor),
the drive must be properly connected to terminals -X155:1 (L1)
to -X155:3 (L3). The supply voltage of the auxiliary equipment must
match the input voltage of the cabinet unit. The load current must not
exceed 10 A and must be set at -Q155 in accordance with the load
connected (see "Electrical installation / Other connections /
Connection for external auxiliary equipment (option L19)").
Set value:
_________________
13 Option L26
Main circuit
breaker (incl.
fuses/circuit
breakers)
In equipment with main circuit breaker, the release current must be
set to match the installation requirements (see "Electrical Installation /
Other connections / Main switch incl. fuses or main circuit breaker
(option L26)").
14 Option L50
Cabinet
illumination with
service socket
The 230 V auxiliary supply for the cabinet illumination with an
integrated service socket must be connected to terminal -X390 and
protected with a fuse (max. 10 A) on the line side (see "Electrical
installation / Other connections / Cabinet illumination with service
socket (option L50)").
15 Option L55
Cabinet anti-
condensation
heating
The 230 V auxiliary supply for the anti-condensation heating for the
cabinet (230 V / 50 Hz, 100 W / or 230 V / 50 Hz 2 x 100 W for
cabinets with a width of 800 to 1200 mm) must be connected to
terminals -X240: 1 to 3 and protected with fuses (max. 16 A) (see
"Electrical installation / Other connections / Anti-condensation heating
for cabinet (option L55)").