Operating instructions
Functions, monitoring, and protective functions
9.3 Drive functions
Drive converter cabinet units
334 Operating Instructions, 10/2008, A5E00288214A
Maximum output frequencies achieved by increasing the pulse frequency
By multiplying the basis pulse frequency (with integers), the following output frequencies can
be achieved (taking into account the derating factors):
Table 9- 5 Maximum output frequency achieved by increasing the pulse frequency
Pulse frequency
[kHz]
Maximum output frequency
[Hz]
1,25 100
2 160
2,5 200
4 300
1)
5 300
1)
1)
The maximum output frequency is limited to 300 Hz due to the closed-loop control.
9.3.9.2 Parameters
• p0009
Device commissioning parameter filter
• p0112
Sampling times pre-setting p0115
• p0113
Selects the minimum pulse frequency
• p0115
Sampling times
• p1800
Pulse frequency