Operating instructions
Output terminals
8.2 Analog outputs
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
297
8.2.1 Lists of signals for the analog outputs
Signals for the analog outputs: vector object
Table 8- 1 List of signals for the analog outputs - vector object
Signal Parameter Unit Scaling (100 %=...)
See table below
Speed setpoint before the setpoint filter r0060 rpm p2000
Motor speed unsmoothed r0061 rpm p2000
Actual speed smoothed r0063 rpm p2000
Output frequency r0066 Hz Reference frequency
Output current r0068 Aeff p2002
DC link voltage r0070 V p2001
Torque setpoint r0079 Nm p2003
Output power r0082 kW r2004
For diagnostic purposes
Control deviation r0064 rpm p2000
Modulation depth r0074 % Reference modulation depth
Torque-generating current setpoint r0077 A p2002
Torque-generating actual current r0078 A p2002
Flux setpoint r0083 % Reference flux
Actual flux r0084 % Reference flux
For further diagnostic purposes
Speed controller output r1480 Nm p2003
I component of speed controller r1482 Nm p2003
Scalings for vector object
Table 8- 2 Scalings for vector object
Variable Scaling parameter Default for quick commissioning
Reference speed 100 % = p2000 p2000 = Maximum speed (p1082)
Reference voltage 100 % = p2001 p2001 = 1000 V
Reference current 100 % = p2002 p2002 = Current limit (p0640)
Reference torque 100 % = p2003 p2003 = 2 x rated motor torque
Reference power 100 % = r2004 r2004 = (p2003 x p2000 x π) / 30
Reference frequency 100 % = p2000/60
Reference modulation depth 100 % = Maximum output voltage
without overload
Reference flux 100 % = Rated motor flux
Reference temperature 100% = 100°C