Operating instructions

Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Drive converter cabinet units
288 Operating Instructions, 10/2008, A5E00288214A
OFF2
Immediate pulse suppression, the drive coasts to standstill.
The motor brake (if parameterized) is closed immediately.
Switching on inhibited is activated.
OFF3
Switch to speed-controlled operation
n_set = 0 is input immediately to brake the drive along the OFF3 deceleration ramp
(p1135).
When standstill is detected, the motor brake (if parameterized) is closed.
The pulses are inhibited when the motor brake closing time (p1217) has elapsed.
Standstill is detected when the speed actual value of the speed threshold (p1226) is
undershot or when the monitoring time (p1227) started when speed setpoint ≤ speed
threshold (p1226) expires.
Switching on inhibited is activated.
Function diagram
FP 6060 Torque setpoint
Parameters
p0341
Motor moment of inertia
p0342
Ratio between the total and motor moment of inertia
p1300
Open-loop/closed-loop control mode
p1499
Accelerating for torque control, scaling
p1501
Change over between closed-loop speed/torque control
p1503
Torque setpoint
p1511
Supplementary torque 1
p1512
Supplementary torque 1 scaling
p1513
Supplementary torque 2
p1514
Supplementary torque 2 scaling
r1515
Supplementary torque total