Operating instructions

Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Drive converter cabinet units
284 Operating Instructions, 10/2008, A5E00288214A
K
p _ n
T
n _ n
p 1460
p 1462
p 1463 x p 1462
p 1461 x p 1460
1
2
3
1
2
3
( n < p 1464 )
( p 1464 < n < p 1465 )
( n > p 1465 )
0 p 1464 p 1465
n
K
p _ n
T
n _ n
,QWHJUDOWLPH
&RQVWDQWORZHUVSHHGUDQJH
ZLWKRXWDGDSWDWLRQ
ZLWKDGDSWDWLRQ
3URSRUWLRQDOJDLQ
$GDSWDWLRQUDQJH
&RQVWDQWXSSHUVSHHGUDQJH
Figure 7-14 Example of speed-dependent adaptation
Function diagram
FP 6050 Kp_n-/Tn_n adaptation
Parameters
p1400.5
Speed control configuration: Kp/Tn adaptation active
Free Kp_n adaptation
p1455
Speed controller P gain adaptation signal
p1456
Speed controller P gain adaptation lower starting point
p1457
Speed amplifier P gain adaptation upper starting point
p1458
Adaptation factor lower
p1459
Adaptation factor upper
p1470
Speed controller encoderless operation P gain
Speed-dependent Kp_n/Tn_n adaptation (VC only)
p1460
Speed controller P gain adaptation speed lower
p1461
Speed controller P gain adaptation speed upper
p1462
Speed controller integral time adaptation speed lower
p1463
Speed controller integral time adaptation speed upper
p1464
Speed controller adaptation speed lower
p1465
Speed controller adaptation speed upper
p1466
Speed controller P gain scaling
Dynamic response reduction field weakening (encoderless VC only)
p1400.0
Speed control configuration: Automatic Kp/Tn adaptation active