6.7 Control via the operator panel
Drive converter cabinet units
240 Operating Instructions, 10/2008, A5E00288214A
Operator input inhibit (factory setting: not active)
Active: The parameters can still be viewed, but a parameter value cannot be saved
(message: "Note: operator input inhibit active"). The OFF key (red) is enabled. The
LOCAL, REMOTE, ON (green), JOG, CW/CCW, INCREASE, and DECREASE keys are
disabled.
Parameterization inhibit (factory setting: not active)
Active: Parameters cannot be changed unless a password is entered. The
parameterization process is the same as with the operator input inhibit. If you try and
change parameters, the message "Note: Parameterization inhibit active" is displayed. All
the control keys can, however, still be actuated.
Access level (factory setting: Expert):
The different parameters required for this complex application are filtered so that they can be
displayed as clearly as possible. You select them according to the access level.
An expert level, which must only be used by expert personnel, is required for certain actions.