Scalings for vector object
Table 6- 14 Scalings for vector object
Size Scaling parameter Default for quick commissioning
Reference speed 100 % = p2000 p2000 = Maximum speed (p1082)
Reference voltage 100 % = p2001 p2001 = 1000 V
Reference current 100 % = p2002 p2002 = Current limit (p0640)
Reference torque 100 % = p2003 p2003 = 2 x rated motor torque
Reference power 100 % = r2004 r2004 = (p2003 x p2000 x π) / 30
Reference frequency 100% = p2000/60
Reference modulation depth 100 % = Maximum output voltage without overload
Reference flux 100 % = Rated motor flux
Reference temperature 100% = 100°C
Object A_INF
Table 6- 15 List of signals for the operation screen - object A_INF
Signal Parameters Short name Unit Scaling (100 %=...) See table
below
DC link voltage smoothed (1) r0026 U_DC V p2001
Input voltage (2) r0025 U_IN V p2001
Active current (3) r0030 IACTV A p2002
Line frequency (4) r0024 FLINE Hz p2000
Active power (5) r0032 PACTV kW r2004
Actual value of current (6) r0027 I_IST A p2002
Temperature of power unit (7) r0037 T_LT °C Reference temperature
Power factor, smoothed (8) r0032 PACTV kW r2004
Modulation depth, smoothed (9) r0028 AUSST % Reference modulation depth
Reactive current component smoothed (10) r0029 IREAC A p2002
Scalings for object A_INF
Table 6- 16 Scalings for object A_INF
Variable Scaling parameter Default for quick
commissioning
Reference frequency 100 % = p2000 p2000 = p0211
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = r0207
Reference power 100 % = r2004 r2004 = r0206
Reference modulation depth 100 % = Maximum output voltage without overload
Reference temperature 100% = 100°C