Operating instructions
Operation
6.7 Control via the operator panel
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
229
6.7.5 Menu: Commissioning / service
6.7.5.1 Drive commissioning
This option enables you to re-commission the drive from the main menu.
Basic Commissioning
Only the basic commissioning parameters are queried and stored permanently.
Complete commissioning
Complete commissioning with motor and encoder data entry is carried out. Following this,
key motor parameters are recalculated from the motor data. The parameter values
calculated during previous commissioning are lost.
In a subsequent motor identification procedure, the calculated values are overwritten.
Motor identification
The selection screen for motor identification appears.
Resetting the fan runtime
After a fan replacement, the time counter for monitoring the fan runtime must be reset.
6.7.5.2 Device commissioning
Device commissioning
In this menu, you can enter the device commissioning status directly. This is the only way
that you can reset parameters to the factory setting for example.
6.7.5.3 AOP30 settings
Control settings
This defines the settings for the control keys in LOCAL mode (see "Operation / Control via
the operator panel / Operation via the operator panel").
Display settings
In this menu, you set the lighting, brightness, and contrast for the display.