Operating instructions
Operation
6.6 PROFIBUS
Drive converter cabinet units
220 Operating Instructions, 10/2008, A5E00288214A
6.6.5.2 Overview of status words and actual values
Table 6- 12 Overview of status words and actual values
Abbreviation Description Parameter Function diagram
ZSW1 Status word 1 (interface mode SINAMICS,
p2038 = 0)
See table "Status word 1 (interface
mode SINAMICS, p2038 = 0)"
FP2452
ZSW1 Status word 1 (interface mode VIK-
NAMUR, p2038 = 2)
See table "Status word 1 (interface
mode VIK-NAMUR, p2038 = 2)"
FP2451
ZSW1_BM Status word 1, metal industry (interface
mode SINAMICS, p2038 = 0)
See table "Status word 1, metal
industry (interface mode SINAMICS,
p2038 = 0)"
FP2428
ZSW2 Status word 2 (interface mode SINAMICS,
p2038 = 0)
See table "Status word 2 (interface
mode SINAMICS, p2038 = 0)"
FP2454
ZSW2_BM Status word 2, metal industry (interface
mode SINAMICS, p2038 = 0)
See table "Status word 2, metal
industry (interface mode SINAMICS,
p2038 = 0)"
FP2429
E_ZSW1 Status word 1 for infeeds See table: "Status word 1 for
infeeds"
FP2457
E_ZSW1_BM Status word 1 for infeeds, metal industry See table: "Status word 1 for
infeeds, metal industry"
FP2430
NIST_A Speed setpoint A (16 bit) r0063[0] FP4715
NIST_B Speed setpoint B (32 bit) r0063 FP4710
IAIST Actual value of current r0068[0] FP6714
MIST Actual torque value r0080[0] FP6714
PIST Actual power value r0082[0] FP6714
NIST_GLATT Actual speed value smoothed r0063[1] FP4715
IAIST_GLATT Current actual value, smoothed r0068[1] FP6714
MIST_GLATT Torque actual value, smoothed r0080[1] FP6714
PIST_GLATT Power actual value, smoothed r0082[1] FP6714
MELD_NAMUR VIK-NAMUR message bit bar r3113, see table "NAMUR message
bit bar"
--
WARN_CODE Alarm code r2132 FP8065
ERROR_CODE Error code r2131 FP8060