Operating instructions
Operation
6.5 Setpoint sources
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
209
6.5.3 Fixed speed setpoints
Description
A total of 15 variable fixed speed setpoints are available.
The default setting specified for the setpoint sources during commissioning via STARTER or
the operating panel makes 3 fixed speed setpoints available. They can be selected via
terminals or PROFIBUS.
Requirement
The default setting for the fixed speed setpoints was chosen during commissioning:
• STARTER:
"Fixed setpoint"
• AOP30:
"4: Fixed setpoint"
Signal flow diagram
)L[HGVSHHGVHWSRLQW
)L[HGVSHHGVHWSRLQW
)L[HGVSHHGVHWSRLQW
)L[HGVSHHGVHWSRLQW
$FWLYH
)6:ELW
)6:ELW
S
S
S
U
Figure 6-19 Signal flow diagram: Fixed speed setpoints
Function diagram
FP 3010 Fixed speed setpoints
Parameter
• p1001
Fixed speed setpoint 01
• p1002
Fixed speed setpoint 02
• p1003
Fixed speed setpoint 03
• r1024
Fixed speed setpoint effective