5.6 Status after commissioning
Drive converter cabinet units
176 Operating Instructions, 10/2008, A5E00288214A
5.6 Status after commissioning
LOCAL mode (control via operator panel)
● You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
● Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
● You specify the setpoint using the "increase" and "decrease" keys or by entering the
appropriate numbers using the numeric keypad.
Analog outputs
● The actual speed (r0063) is output as a current output in the range 0 to 20 mA at analog
output 0 (X522:2 and 3).
A current of 20 mA is equal to the maximum speed in p1082.
● The actual current value (r0068) is output as a current output in the range 0 to 20 mA at
analog output 1 (X522:5 and 6).
A current of 20 mA corresponds to the current limit (p0640), which is set to 1.5 x the rated
motor current (p0305).
Digital outputs
● The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
● The “no fault active” signal is output at digital output 1 (X542:5 and 6) (fail safe).
● The "ready to start" signal is output at digital output 8 (X541:2).