Operating instructions

Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
155
Select the required data:
Technological application:
"Standard drive (VECTOR) (0)"(default setting)
Edge modulation is not enabled.
The dynamic voltage reserve is increased (10 V), which reduces the maximum output
voltage.
"Pumps and fans (1)"
Edge modulation is enabled.
The dynamic voltage reserve is reduced (2 V), which increases the maximum output
voltage.
"Passive loads (for sensorless control down to f = 0) (2)"
Controlled operation down to standstill is possible for passive loads.
These include applications in which the load cannot produce a regenerative torque on
startup and the motor comes to a standstill when pulses are inhibited.
Motor identification:
"Motor data identification with motor running" is normally the appropriate default setting
for SINAMICS S150, especially if an encoder is used for speed control.
Click Continue >