Operating instructions
Commissioning
5.3 Procedure for commissioning via STARTER
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00288214A
139
Configuring the drive unit properties
Figure 5-17 Configuring the drive unit properties
⇒ Under Standard:, choose the appropriate standard for your motor,
whereby the following is defined:
● IEC motor (50 Hz, SI unit): Line frequency 50 Hz, motor data in kW
● NEMA motor (60 Hz, US unit): Line frequency 60 Hz, motor data in hp
⇒ Under Connection voltage: the DC link voltage of the cabinet unit is specified (this should
not be changed).
⇒ Under Power unit application: choose the appropriate application for your drive unit:
● Load duty cycle with high overload condition for vector drives (factory setting)
● Load duty cycle with slight overload condition for vector drives
⇒ Click Continue >