User Manual
8 VEGACOM 557 Siemens
Product description
Indicating elements
LED in front plate
- green "BA" signal for active communication via
3964/3964 R
- red (flashing) DISBUS/LOGBUS failure
- red (on) failure
- green "on" operating condition
Ambient conditions
Permissible ambient temperature -20°C … +60°C
Storage and transport temperature -20°C … +85°C
Moisture 93 %, T = 40°C acc. to DIN/IEC 68-2-3
Shock load 2 … 100 Hz, 0.7 g
Electrical protective measures
Protection:
not mounted IP 00
in carrier BGT 596
or BGT LOG 571
- front side completely equipped IP 40
- upper and lower side
BGT 596 IP 00
BGT LOG 571 IP 20
- wiring side IP 00
in housing type 505
- front side IP 40
- other sides IP 30
Protection class II (in housing type 505)
Overvoltage category II
Mechanical data
Series module card for
- carrier BGT 596
- carrier BGT LOG 571
- housing type 505
Dimensions, not mounted W = 25.4 mm (5 TE), H = 128.4 mm,
D = 166 mm + strap
Weight approx. 200 g
CE conformity
VEGACOM 557 meets the protective regulations of EMC (89/336/EWG) and NSR
(73/23/EWG). Conformity has been judged acc. to the following standards:
EMC Emission EN 50 081 - 1: 1993
Susceptibility EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993