User Manual

VEGACOM 557 Siemens 31
S5 functional component
Call up of the Fetch and Receive component for the relay information
...
FB 2 C:CP524_ST.S5D LAE = 62
Network 1 0000 Output
Name :REL
:O M 1.1
:ON M 1.1 VKE = 1 force, so that FETCH
: is worked on in any case
:
:SPA FB 246 enquire FETCH-component
Name :FETCH
SSNR : KY 0,0 Interface no. = 0
A-NR : KY 0,2 Order number = 2 for relay information
ANZW : MW 11 Indication double word up from MW11
ZTYP : KC DB Data destination(the indication values) in data component
DBNR : KY 0,4 ... Number 3
ZANF : KF +0 Data destination to DW0
ZLAE : KF +32 32 words (all relays)
PAFE : MB 4 Parametr.failure in MB 4
:
:
:
:
:
:
:
:O M 1.1
:ON M 1.1 VKE = 1 force, so that FETCH
: is worked on in any case
:
:SPA FB 245 enquire RECEIVE-component
Name :RECEIVE
SSNR : KY 0,0 Interface no. = 0
A-NR : KY 0,0 Order number = 1
ANZW : MW 12 Indication double word up from MW12
ZTYP : KC DB Data destination in data component
DBNR : KY 0,0
ZANF : KF +0
ZLAE : KF +0
PAFE : MB 3
:
:
:
:
:
:
:BE
Note:
In the total program only one RECEIVE necessary.