User Manual
14 VEGACOM 557 Siemens
1
ON EPG
2345678 1
ON EPG
23456781
ON EPG
2345678
DIL switch 3 additional board
(negligible)
Switch position (factory setting)
Procedure Siemens 3964 R
Data transmission 9600 baud
Number of data bits 8
Parity even
physical interface RS 232
DIL switch DIL switch DIL switch
12 3
3.2 Settings on the CP 524
Interface number
The interface number is required in the S5
program for addressing of the communication
processor and can be set with J53. As a
standard feature all bridges are closed (inter-
face number = 0).
CP instrument interface
3 instrument interfaces are available. An
RS 232, a TTY and a RS 422 / 485 interface
module. Depending on the interface used in
the CP, the assignment of the connections on
VEGACOM 557 (see multiple plug) must be
taken into consideration and the setting of the
DIL switches must be made on the
VEGACOM additional board.
Addressing of the process signals
DIL switch 2 additional board
Selection of the baud rate
SW 8 SW 7 SW 6
OFF OFF OFF 300 Baud
ON OFF OFF 600 Baud
OFF ON OFF 1200 Baud
ON ON OFF 2400 Baud
OFF OFF ON 4800 Baud
ON OFF ON 9600 Baud
OFF ON ON 19200 Baud
ON ON ON 38400 Baud
Number of data bits
SW 5
ON 8 data bits
OFF 7 data bits
Parity
SW 4 SW 3
OF F OF F without parity
OF F O N without parity
ON OFF odd parity (ODD)
ON O N even parity (EVEN)
Protocol mode
SW 2
O F F Siemens 3964
ON Siemens 3964 R
DCS measured value image
SW 1
O F F all measured values MET1
all measured values MET2
O N 1 measured value MET 1
1 measured value MET 2