User guide

46 VEGACOM 557 Profibus DP
Setup
8 Setup
8.1 Setup check list
For the setup of VEGACOM 557 on PROFI-
BUS DP proceed as follows:
I. Check hardware requirements
PROFIBUS DP compatible master compo
nent
VEGACOM 557 version Profibus DP
II. Check software requirements
VEGA Utility diskette from version 3.00 with
GSD file and programming examples for
Siemens S5, S7
II. Carry out adjustments on VEGACOM
557 (DIL switch on additional board)
Set Profibus-Slave address
Activate/deactivate bus terminator
III. Configurate Profibus DP-Master and
check communication
The green LED named BA lights on
VEGACOM 557 with correct communica-
tion.
8.2 Setup SIEMENS S7 automation
system
For connection of decentralised peripherals
to automation instruments of S7 series,
SIEMENS uses Pr ofibus DP. Many of the S7
CPUs offer already a Profibus DP interface.
For connection of VEGACOM 557 to a S7
automation system, a Profibus DP interface
must be available and the automation system
must work as Pr ofibus-Master. In this section,
all measures that must be taken for the setup
of your VEGACOM 557 on a S7 automation
system are described in detail.
Note:
If your Profibus-Master is manufactured by
another company, please check the manu-
facturer documentation for the r equired infor -
mation.
Configuration SIEMENS S7 automation
system
The configuration and parameter setting of
the Profibus is done with the software
SIMATIC-Manager fr om SIEMENS. All con-
figurations for the connected Profibus net-
work are made via the window HW-Config.