Operating Instructions Pluggable display and adjustment module for plics® sensors PLICSCOM Document ID: 36433
Contents Contents 1 About this document 1.1 Function ............................................................................. 3 1.2 Target group ....................................................................... 3 1.3 Symbolism used ................................................................. 3 2 For your safety 2.1 Authorised personnel ......................................................... 4 2.2 Appropriate use .................................................................. 4 2.
1 About this document 1 About this document 1.1 Function 1.2 Target group 1.3 Symbolism used This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device. This operating instructions manual is directed to trained specialist personnel.
2 For your safety 2 2.1 For your safety Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use The pluggable display and adjustment module is used for measured value indication, adjustment and diagnosis.
2 For your safety You can find the conformity certificate in the download section of our homepage. 2.6 NAMUR recommendations NAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are accepted as the standard in field instrumentation. The device fulfills the requirements of the following NAMUR recommendations: • NE 53 – Compatibility of field devices and display/adjustment components For further information see www.namur.de. 2.
3 Product description 3 Scope of this operating instructions manual 3.1 Configuration This operating instructions manual applies to the following hardware and software versions of the display and adjustment module: • Hardware from 1.0.0 Software from 1.0.0 • Instrument versions Product description The indicating/adjustment module consists of a display with full dot matrix as well as four keys for adjustment.
3 Product description 1 Fig. 1: Mounting the display and adjustment module in the single chamber housing 1 Mounting in the electronics compartment 1 2 Fig. 2: Mounting the display and adjustment module in the double chamber housing 1 2 Mounting in the electronics compartment Mounting in the connection compartment The electrical connection is carried out via spring contacts in the sensor and contact surfaces in the display and adjustment module.
3 Product description Parallel operation of display and adjustment modules Sensors with hardware version < 2.0.0, software version < 3.99 With these sensors, the interface for the display and adjustment module and the external display and adjustment unit are connected internally. Operating two display and adjustment modules in parallel, i.e. one in the sensor and one in the external display and adjustment unit, is thus not possible. 1 Display I2C 1 2 5 6 7 8 2 Fig.
3 Product description 1 4...20mA (+)1 2 (-) 2 5 6 7 8 Fig. 5: Interfaces for display and adjustment 1 2 Spring contacts for display and adjustment module Terminals for the external display and adjustment unit Connection of more than one display and adjustment module on one interface or a total of more than two display and adjustment modules, however, is not supported.
3 Product description Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
4 Prepare setup 4 4.1 Prepare setup Insert display and adjustment module The display and adjustment module can be inserted into the sensor and removed any time. Four positions displaced by 90° can be selected. It is not necessary to interrupt the power supply. Proceed as follows: 1. Unscrew the housing cover 2. Place the display and adjustment module in the requested position onto the electronics and turn to the right until it snaps in 3.
4 Prepare setup 1 2 Fig. 7: Insertion of the display and adjustment module with double chamber housing 1 2 In the electronics compartment In the connection compartment (with Ex-d-ia version not possible) Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. 4.2 Adjustment system 1 2 Fig.
4 Prepare setup • – Save value • [->] key: – Presentation change measured value – Select list entry – Select editing position • [ESC] key: – interrupt input – Jump to next higher menu The sensor is adjusted via the four keys of the display and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered.
5 Setup - Sensors up to software 3.99 5 Setup - Sensors up to software 3.99 5.1 Common adjustment menu for all signal outputs Through the parameter adjustment the instrument is adapted to the application conditions. The parameter adjustment is carried out via an adjustment menu. Information: In this operating instructions, all general parameters are described. Additional instrument-specific parameters are described in the operating instructions of the respective sensor.
5 Setup - Sensors up to software 3.99 cal or spherical tanks - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and the vessel volume. The linearization applies to the measured value indication and the current output. By activating the appropriate curve, the volume percentage of the vessel is correctly displayed. If the volume should not be displayed in percent but e.g.
5 Setup - Sensors up to software 3.99 • Min. and max. temperature: ultrasonic sensors, pressure transmitters Peak value Diagnosis/Measurement reliability When non-contact level sensors are used, the measurement can be influenced by the respective process conditions. In this menu item, the measurement reliability of the level echo is displayed as dB value. The measurement reliability equals signal strength minus noise. The higher the value, the more reliable the measurement.
5 Setup - Sensors up to software 3.99 Information: The trend recording is not activated when being shipped. It must be started by the user via the menu item "Start trend curve". A comparison of the echo curve and the false echo curve allows a more detailled evaluation of measurement reliability. The selected curve is updated continuously. With the [OK] key, a submenu with zoom functions is opened.
5 Setup - Sensors up to software 3.99 The simulation is now running, with 4 … 20 mA/HART a current is outputted and with Profibus PA or Foundation Fieldbus a digital value. How to interrupt the simulation: → Push [ESC] Information: The simulation is automatically terminated 10 minutes after the last press of a key. Simulation Start simulation? Service/Reset With the reset function, modified values are reset.
5 Setup - Sensors up to software 3.99 Service/Language The sensor is already set to the ordered national language. In this menu item you can change the language. The following languages are available, e.g. in software version 3.
5 Setup - Sensors up to software 3.99 In this menu item, the PIN is activated/deactivated permanently. Entering a 4-digit PIN protects the sensor data against unauthorized access and unintentional modifications. If the PIN is activated permanently, it can be deactivated temporarily (i.e. for approx. 60 min.) in any menu item. The instrument is delivered with the PIN set to 0000.
5 Setup - Sensors up to software 3.99 The following values can be displayed: • Height Pressure (only with pressure transmitters) Distance (only with radar, guided microwave, ultrasonics) Current Scaled Percent Lin. percent Temperature (only with pressure transmitters). • • • • • • • • The selection "scaled" opens the menu items "Display unit" and "Scaling".
5 Setup - Sensors up to software 3.99 Current output Characteristics 4 … 20 mA Failure mode4) Hold value 20 … 4 mA 20.5 mA 22 mA < 3.6 mA Min. current 5) Max. current 3.8 mA 4 mA 6) 20 mA 20.5 mA The values in bold font represent the data of the factory setting. In HART multidrop mode, the current is constantly 4 mA. This value does not change even in case of failure. Current output Characteristic: 4-20 mA ▼ Failure mode: 22 mA ▼ Min. current 3.
5 Setup - Sensors up to software 3.99 HART mode Standard Address 0 The default setting is standard with address 0. 5.3 Adjustment menu Profibus PA Level and pressure sensors operate as slaves on the Profibus PA. To be identified as a bus participant, each sensor must have a unique address. Each instrument is delivered with address 126. With this address, it can at first be connected to an existing bus. However, the address must be changed. This can be done in this menu item.
5 Setup - Sensors up to software 3.99 • PA-Out (value after passing the function block): PA output Temperature • In the menu item "Display" you can define which value should be indicated on the display. Displayed value PA-Out Profibus transmits two values cyclically. The first value is determined in the menu item "Channel". The selection of the additional cyclical value is made in the menu item "Additional PA value".
36433-EN-130228 5 Setup - Sensors up to software 3.
6 Setup - radar sensors from software 4.0.0 6 Setup - radar sensors from software 4.0.0 6.1 Common adjustment menu for all signal outputs Through the parameter adjustment the instrument is adapted to the application conditions. The parameter adjustment is carried out via an adjustment menu. Information: In this operating instructions, all general parameters are described. Additional instrument-specific parameters are described in the operating instructions of the respective sensor.
6 Setup - radar sensors from software 4.0.0 You can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular designation must be entered for exact identification of individual measuring points. The available digits comprise: • Letters from A … Z Numbers from 0 … 9 Special characters +, -, /, - • • In this menu item, the PIN is activated/deactivated permanently.
6 Setup - radar sensors from software 4.0.0 In the delivery status, the sensor is set to the ordered national language. Display/Backlight The optionally integrated background lighting can be adjusted via the adjustment menu. The function depends on the level of the supply voltage, see operating instructions of the respective sensor. The lighting is switched off in the delivery status. In this menu item, the device status is displayed. Diagnosis/Electronics temperature The respective min. and max.
6 Setup - radar sensors from software 4.0.0 Additional adjustments/ Linearization A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e. g. horizontal cylindrical or spherical tanks - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and the vessel volume.
6 Setup - radar sensors from software 4.0.0 In this menu item, the internal clock of the sensor is adjusted. Additional adjustments/ Date time Additional adjustments/ The instrument settings are copied with this function. The following Copy instrument settings functions are available: • Store data from the sensor into the indicating/adjustment module.
6 Setup - radar sensors from software 4.0.0 Info/Instrument version In this menu item, the hardware and software version of the sensor is displayed. Info/Calibration date In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module or via the PC.
6 Setup - radar sensors from software 4.0.0 Setup/Current output Min./Max. In the menu item "Current output Min./Max.", you determine the reaction of the current output during operation. The default setting is min. current 3.8 mA and max. current 20.5 mA. Display/Displayed value In this menu item you can define the indication of the measured value on the display. The default setting for the indication value is e.g. distance with radar sensors.
6 Setup - radar sensors from software 4.0.0 How to start the simulation: 1. Push [OK] 2. Select the requested simulation variable with [->] and confirm with [OK]. 3. With [OK] you start the simulation, first of all the actual measured value is displayed in % 4. Start the editing mode with [OK] 5. Set the requested numerical value with [+] and [->]. 6. Push [OK] Note: During simulation, the simulated value is outputted as 4 … 20 mA current value and digital HART signal.
6 Setup - radar sensors from software 4.0.0 are carried out.
6 Setup - radar sensors from software 4.0.0 In the menu item "Display" you can define which measured value should be presented on the display.
6 Setup - radar sensors from software 4.0.0 5. Set the requested numerical value with [+] and [->] 6. Push [OK] Note: During simulation, the simulated value is outputted as Profibus PA signal. How to interrupt the simulation: → Push [ESC] Information: The simulation is automatically terminated 10 minutes after the last press of a key.
6 Setup - radar sensors from software 4.0.0 In this menu item, the Profibus ident number of the instrument is displayed. Info/Profibus Ident Number 6.4 Adjustment menu Foundation Fieldbus In the menu item "Display" you can define which measured value should be presented on the display.
6 Setup - radar sensors from software 4.0.
7 Maintenance and fault rectification 7 Maintenance and fault rectification 7.1 Maintenance 7.2 How to proceed in case of repair If the device is used correctly, no maintenance is required in normal operation. You can find a repair form as well as detailed information on how to proceed under www.vega.com/downloads and "Forms and certificates". By doing this you help us carry out the repair quickly and without having to call back for needed information.
8 Dismounting 8 8.1 Dismounting Dismounting steps Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. 8.2 Disposal The instrument consists of materials which can be recycled by specialised recycling companies.
9 Supplement 9 9.1 Supplement Technical data General data Weight approx. 150 g (0.
9 Supplement 9.3 Industrial property rights Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте VEGA系列产品在全球享有知识产权保护。 进一步信息请参见网站< 9.4 >。 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/ originator.
INDEX INDEX A Additional PA value – Primary Value 24 – Secondary Value 24 Adjustment system 13 Application area 6 B Backlight 15, 28 C Channel 33 Channel with Profibus PA 23 Copy sensor data 19 Copy sensor settings 30 Current output 22 Current output Min./Max.
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information available at the time of printing. Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2013 VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info.de@vega.com www.vega.