Owner manual
Pressure transmitter D81 METEC
®
29
Setup
Blocked menu. The
following menu window is
indicated but not supported
by the sensor. Therefore
saving of adjustments
carried out here is not
possible.
6 PV Damping
1.1.3
1.2
1.3
1.4
1.5
1.1.2
1.1.1
1.3.1
1.3.2
1.3.3
1.3.4
1.3.6
6 Write protect
7 Description
8 Message
9 PV Snsr. s/n
Final asmbly num 0
Revision #’s
1.2.3
1.2.2
Input of individual current
values for test purposes
(simulation of measured
value)
NAECH VERL.
Empty and full
adjustment
with medium
(see next page)
see next
page
see next
page
CC
CC
C
DD
DD
D
Newly assigned
measurement loop
designation to be
saved with ENTER
and SEND
}
}
see next
page
}
Transmission function
(linear)
Safety
enquiry
acknowl-
edgement
A1A1
A1A1
A1
B1B1
B1B1
B1
}
Generic: SENSOR
Detailed setup
1 Sensors
2 Signal condition
3 Output condition
4 Device information
SAVE HOME
Generic: SENSOR
PV
83.454 mbar
HELP EXIT
Generic: SENSOR
PV % rnge
83.385 %
HELP EXIT
Generic: SENSOR
AO1
17.327 mA
HELP EXIT
Generic: SENSOR
PV Snsr unit
mbar
mbar
g/cm2
kg/cm2
Pa
ESC ENTER
Generic. D84
Range values
1 PV LRV 0.000 mbar
2 URV 100.000 mbar
3 PV LSL 0.000 mbar
4 USL 100.000 mbar
HELP HOME
Generic: SENSOR
PV Damp
1.000 s
1 .000 s
HELP DEL ESC ENTER
Generic: SENSOR
Basic setup
1Tag
2 PV Unit
3 Range values
4 Device information
5 PV Xfer fnctn
HELP SAVE HOME
Generic: SENSOR
Review
Model
Generic
HELP PREV NEXT EXIT
Generic: SENSOR
Calibration
1 Apply values
2 Enter values
HELP SAVE HOME
Generic: SENSOR
Choose analog output
level
14 mA
2 20 mA
3 Other
4End
ABORT ENTER
Generic: SENSOR
Diag/Service
1 Test device
2 Loop test
3 Calibration
4 D/A trim
SAVE HOME
Generic: SENSOR
Device information
1 Distributor
2 Model Generic
3 Dev id 11017815
4Tag D84
5 Date 10/01/97
HELP SAVE HOME
Generic: SENSOR
Tag
BAR 20
BAR 20
HELP DEL ESC ENTER