User Manual

Capacitive electrodes EL - Profibus PA 43
Sensor parameter adjustment – Out-
puts
In this window, you can change the preset
values for the PA output and the measured
value display. Push the button
Save
to trans-
fer the modified values.
Click in the window "Instrument data param-
eter adjustment" to Outputs.
Setup
Push the button
Transfer
, to call up further
linearisation curves.
In the window "Linearisation", you can choose
the linearisation curves of a horizontal cylin-
drical tank or a spherical tank. If you choose
a user-programmable curve, you can then
click to Edit and open the program "Tank
Calculation". With this program, you can cal-
culate the curves of different tank forms (see
the manual "VEGA Visual Operating"). After
the selection of the curve, click to OK.
Sensor parameter adjustment – Inte-
gration time
Choose this function if you want to set an
integration time (damping).
The range for the integration time is between
0 and 600 seconds. As a standard feature,
an integration time of zero seconds is preset.
After the set integration time has expired,
63 % of the measured value change remain
on the output.
In the window "Instrument data parameter
adjustment", you click to Conditioning.
Click in the window "Conditioning" to Integra-
tion time.
In the window "Integration time" you can enter
a time of max. 600 seconds. Then click to
OK.