Manual

Capacitive electrodes EK - Profibus PA 15
ser. no. 10612892
Product description
1.6 Type plate
Before mounting and electrical connection,
please make sure you are using a suitable
instrument. Note the type plate which is
located as shown below:
Type plate
The type plate contains important data
required for mounting and connection. The
configuration and elements of the type plate
are hence explained in the following example.
Contents of the type plate (example)
6
VEGA
®
EK 11
type EK11EXO.XGBVSTXXVKXX
see PTB Nr. EX-98.E.2085 EEx ia IIC T6 0032
PTB 98 ATEX 2086 II 1/2G EEx ia IIC T6
techn. data see document. / certificates 1998
protection: IP 66/67 Insp.
length: 400mm VVO: 02
Ord. no. 123456/000
3
1
4
2
®
D-77757 Schiltach
5
Z-65.13.XXX
7
8
9
2
1 Master data of the order number
1 Configuration of the type plate (example)
2 Ex certification number
Explosion protection version - note the
information and regulations of the certificate
3 Data of the electronics/approvals
4 No. of the order confirmation/pos. no.
5 Number of the electrode type
6 Serial number
7 Test mark when used as part of an overfill
protection system for vessels storing water
endangering liquids - note the information
and regulations of the general type
approval
8 Year of manufacture
9 Number of the test authority
Order code
You can find detailed information on the order
code in the "Product Information Capacitive"
or in the "VEGA price list".