Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter I - page 25
FUNCTION OF THE SW1, SW2, SW4-SW5, SW7, SW9-SW10-
SW11 & SW12 JUMPERS OF THE BG15 BOARD
SW1
When the jumper is present, 24V increase the mass relays.
SW2
When the jumper is present, 0V increases the mass relays.
SW3
DOES NOT EXIST.
SW5
1
2
3
SW4
1
2
3
SW5
1
2
3
SW4
1
2
3
When the jumpers are in the lower (position 1-2) the controller is
programmed for use with the P202U tape-head.
When the jumpers are in the upper (position 2-3) the controller is
programmed for use with the O03 tape-head or the I.L.S proximity switches.
SW6
DOES NOT EXIST.
SW7
1
2
3
SW7
1
2
3
When the jumper is in the lower (position HYDR) the controller is
programmed for use as a HYDRAULIC.
When the jumper is in the upper (position TRAC) the controller is
programmed for use as a TRACTION.
SW8
DOES NOT EXIST.
SW9
SW10
SW11
SW12
1 2 3
SW9
SW10
SW11
SW12
1 2 3
Place the jumper to the right (position 2-3) for a single button - 2 to 8 floors
using on the BG15 board only.
Place the jumper to the left (position 1-2) for all other situations.