Installation manual

Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 91
OUTPUTS DEFINITIONS
Ram Address
19
:
best displayed in segment mode.
Segment
0
to
7
:
QM0-7
(Hall Call Registration Lights for Up 0
to 7) (S ELEC).
They show us respectively the state of the Hall Call Registration Lights for Up, QM0 to
QM7.
Outputs QM0 to QM7 are the terminals MX to M7.
The corresponding segments are on when the Outputs are activated and give out 0 Volts.
The corresponding segments are off when the Outputs are de-activated and give out 24
Volts.
Ram Address
1A
:
best displayed in segment mode.
Segment
0
to
7
:
QM8-15
(Hall Call Registration Lights for Up 8
to 15) (S ELEC).
They show us respectively the state of the Hall Call Registration Lights for Up, QM8 to
QM15.
Outputs QM8 to QM15 are the terminals M8 to M15.
Ram Address
1C
:
best displayed in segment mode.
Segment
1
to
7
:
QD1-7
(Hall Call Registration Lights for Down 1
to 7) (S ELEC).
They show us respectively the state of the Hall Call Registration Lights for Down, QD1 to
QD7.
Outputs QD1 to QD7 are the terminals D1 to D7.
The corresponding segments are on when the Outputs are activated and give 0 Volts.
The corresponding segments are off when the Outputs are de-activated and give 24 Volts.
Segment
0
:
Not used
Ram Address
1D
:
best displayed in segment mode (S ELEC).
Segment
0
to
7
:
QD8-15
(for Down 8 to 15).
They show us respectively the state of the Hall Call Registration Lights for down QD8 to
QD15.
Outputs QD8 to QD15 are the terminals D8 to D15.