Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 81
INPUTS DEFINITIONS
• Ram Address
0E
:
best displayed in segment mode.
Segment
7
: Not used.
Segment
6
:
ZONE
(Door Zone Relay).
This shows us whether the shunting device DONNE the door zone or not.
Segment 6 is on if the device is in the zone.
Segment 6 is off in the reverse case.
Segment
5
: Not used.
Segment
4
:
PRIC
(Car Priority).
This shows us the state of the car priority contact. (PRIC and 0V).
Segment 4 is on when the contact is closed to command the car priority function.
Segment 4 is off in the reverse case.
Segment
3
:
NS
(Non-Stop).
This shows us the state of the Non-stop contact (NS and 0V).
Segment 3 is on when the contact is closed to command the Non-Stop function.
Segment 3 is off in the reverse case.
Segment
2
:
SUSD
(Delayed Departure).
This shows us the state of the delayed departure contact (SUSD and 0V).
Segment 2 is on when the contact is closed to command the delayed departure.
Segment 2 is off in the reverse case.
Segment
1
:
MHS
(Out of Service).
This shows us the state of the Out of Service contact (MHS and 0V).
Segment 1 is on when the contact is closed to command the Switch to out of Service
function.
Segment 1 is off in the reverse case.
Segment
0
:
POM
(Fireman Service).
This shows us the state of the Fireman Service contact (POM and 0V).
Segment 0 is on when the contact is closed, i.e., when the Fireman Service function is
commanded.
Segment 0 is off in the reverse case.