Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 74
PARAMETER DEFINITIONS
• Par Address
7B
: best displayed in segment mode.
Segment
7
: Not used.
Segment
6
: Not used.
Segment
5
: Not used.
Segment
4
: Not used.
Segment
3
:
We program segment 3 to " 1 " when we want to use the programmable output 4 (SPG4)
for the AUTOMATIC LIGHT (LU).
We program segment 3 to " 0 " in the reverse case.
Segment
2
:
We program segment 2 to " 1 " when we want to use the programmable output 3 (SPG3)
for the AUTOMATIC LIGHT (LU).
We program segment 2 to " 0 " in the reverse case.
Segment
1
:
We program segment 1 to " 1 " when we want to use the programmable output 2 (SPG2)
for the AUTOMATIC LIGHT (LU).
We program segment 1 to " 0 " in the reverse case.
Segment
0
:
We program segment 0 to " 1 " when we want to use the programmable output 1 (SPG1)
for the AUTOMATIC LIGHT (LU).
We program segment 0 to " 0 " in the reverse case.
• Par Address
7E
:
CAADDEF
(Last But One Fault Code) best displayed in
hexadecimal.
At this address, the Series 32 gives the fault code 3.
• Par Address
7F
:
CDEFPA
(Oldest Fault Code) best displayed in hexadecimal.
At this address, the Series 32 gives the fault code 4.