Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 73
PARAMETER DEFINITIONS
• Par Address
7A
: best displayed in segment mode.
Segment
7
:
We program segment 7 to " 1 " when we want to use the programmable output 4 (SPG4)
to inhibit (INH1).
(See parameter address 63, segments 4 to 7).
We program segment 7 to " 0 " in the reverse case.
Segment
6
:
We program segment 6 to " 1 " when we want to use the programmable output 3 (SPG3)
to INHIBIT (INH1).
(See parameter address 63, segments 4 to 7).
We program segment 6 to " 0 " in the reverse case.
Segment
5
:
We program segment 5 to " 1 " when we want to use the programmable output 2 (SPG2)
to INHIBIT (INH1).
(See parameter address 63, segments 4 to 7).
We program segment 5 to " 0 " in the reverse case.
Segment
4
:
We program segment 4 to " 1 " when we want to use the programmable output 1 (SPG1)
to INHIBIT (INH1).
(See parameter address 63, segments 4 to 7).
We program segment 4 to " 0 " in the reverse case.
Segment
3
:
We program segment 3 to " 1 " when we want to use the programmable output 4 (SPG4)
for the fire service light (VPMP).
We program segment 3 to " 0 " in the reverse case.
Segment
2
:
We program segment 2 to " 1 " when we want to use the programmable output 3 (SPG3)
for the fire service light (VPMP).
We program segment 2 to " 0 " in the reverse case.
Segment
1
:
We program segment 1 to " 1 " when we want to use the programmable output 2 (SPG2)
for the fire service light (VPMP).
We program segment 1 to " 0 " in the reverse case.
Segment
0
:
We program segment 0 to " 1 " when we want to use the programmable output 1 (SPG1)
for the fire service light (VPMP).
We program segment 0 to " 0 " in the reverse case.