PARAMETER DEFINITIONS
Segment
1
:
OUAVAR
(Open Before Stop).
We program segment 1 to " 1 " if we want to carry out the Open Before Stop function and
thus operate the safety chain N66 nudging device.
We program segment 1 to " 0 " in the reverse case.
Segment
0
:
TPRAL
(Door Lengthening Time).
We program segment 0 to " 1 " if we want the base unit of the door timings to go from 1 to
2.5 seconds, thus allowing us to have times from 5 seconds to 10 minutes.
We program segment 0 to " 0 " in the reverse case.
Par Address
64
:
TIRP2
(Reversal Time of the Door 2 Relays) best displayed in hex.
At this address, we program the time which runs from the instant the Serie 32 releases the
closure relay to when it activates the door 2 open relay .
This timing is programmed at intervals of between 10 ms and 2.55 seconds.
See page 94 for the conversion between decimal and hex, from 0 to 255 ....... 00 to FF.
Par Address
67
:
TIGPO2
(Door 2 Integrator Time) best displayed in hexadecimal.
At this address, we program the timing of the door 2 integrator in seconds and in hex.
We can program a value from 1 to 255 seconds.
See page 94 for the conversion between decimal and hex, from 0 to 255 ....... 00 to FF.
If we program 00, there will be no Door Integrator.
Par Address
68
:
TIGPO2
best displayed in segment mode.
At this address, we define the door 2 functioning for level 0.
Segment
7
: Not used.
Segment
6
: Not used.
Segment
5
: Not used.
Segment
4
:
PORCAB2N0
(Car Door 2 at Level 0).
We program segment 4 to " 1 " when a car equipped with an automatic door commanded
by the Series 32 relays (the landing doors are of the swing variety).
We program segment 4 to " 0 " with a flush shaft or with an automatic car driven by just 1
retiring ramp or with an automatic car and landing.