Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 68
PARAMETER DEFINITIONS
• Par Address
62
:
TREP2
(Re-Opening Time of Door 2)
best displayed in
hexadecimal.
At this address, we program the time during which door 2 stays open after having caused
a RE-OPENING.
This timing is programmed into seconds and hex.
Its value must be between 1 and 255 seconds.
See page 94 for the conversion between decimal and hex, from 0 to 255 ....... 00 to FF.
• Par Address
63
: best displayed in segment mode.
Segment
7
:
CABVID
(Empty Car Option).
We program segment 7 to " 1 " when we want the A191 to operate the EMPTY CAR
option.
This option consists of erasing all the requests for the car if after 3 stops the light cell has
not been broken.
We program segment 7 to " 0 " in the reverse case.
Segment
6
:
SHTCS
(CS Nudging Option).
We program segment 6 to " 1 " when we want the A191 to nudge the CS option after
the time programmed into address 62 has elapsed and if a request has been
registered. Furthermore, we activate output " INH1 " which feeds a buzzer to inform
passengers that the door will be re-closing.
(See output position - parameter address 7A, segments 4 to 7 on page 88).
We program segment 6 to " 0 " in the reverse case.
Segment
5
:
ISO
(Re-Levelling).
We program segment 5 to " 1 " if we want the RE-LEVELLING option (open AND closed
doors).
We program segment 5 to " 0 " in the reverse case.
Segment
4
:
RMLIFT
(MLift Regulator).
We program segment 4 to " 1 " if we want to drive an MLift variable frequency speed
regulator
We program segment 4 to " 0 " in the reverse case.
Segment
3
: Not used.
Segment
2
:
REGUL
(REGULator).
We program segment 2 to " 1 " when we want to drive an independent speed regulator.
We program segment 2 to " 0 " in the reverse case.