Installation manual

Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 67
PARAMETER DEFINITIONS
Segment
5
:
P2SFCOU
(Door 2 without Open Limit).
We program segment 5 to " 1 " when we wish to operate Door 2 in the open direction
without looking for a door open limit (FCOU).
We program segment 5 to " 0 " when we want to operate an automatic door equipped with
a close limit switch (FCOU).
Segment
4
:
P2SFCFE
(Door 2 without Closed Limit).
We program segment 4 to " 1 " when we want to operate Door 2 in the close direction
without looking for a door close limit (FCFE).
We program segment 4 to " 0 " when we want to operate an automatic door equipped with
a closure limit switch (FCFE).
Segment
3
:
PMAFCP2
(Door 2 Extended Close Time).
We program segment 3 to " 1 " when we want to maintain movement for an additional 300
ms after the closed limit has been reached.
We program segment 3 to " 0 " when we want to stop the movement from when door 2 has
reached the closed limit.
Segment
2
:
MSTPMP2
(Keep Power On whilst Door 2 in
Operation).
We program segment 2 to " 1 " when we want to keep door 2 motor on during operation.
We program segment 2 to " 0 " in the reverse case.
Segment
1
:
AMPSEC2
(Stopping of Door 2 Movement on arrival
of Safety Chain).
We program segment 1 to " 1 " when we want to operate a door without having reached
the closed limit and which has a tendency to re-open when the motor is no longer fed.
Having lost 8 from the safety chain, we once more give a close signal to re-gain 8. The
door will continue to bang if this option is not programmed. Indeed, the motor ceases to be
fed the first time 8 appears.
With this type of door, we always program the Closing Forced when Moving option.
We program 0 to " 0 " when this option is not required.
Segment
0
:
MSTPRP2
(Keep Door 2 Power Permanently On).
We program segment 0 to " 1 " when we want to keep the door 2 motor operator
permanently on when opening and closing.
We program segment 0 to " 1 " in the reverse case.
Par Address
61
:
TP02
(Timing of Door N° 2) best displayed in hexadecimal.
At this address, we program the timing of door 2 in seconds and hex.
We can program a value from 2 to 255 seconds.
See page 94 for the conversion between decimal and hex, from 0 to 255 ....... 00 to FF.