Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 65
PARAMETER DEFINITIONS
Segment
0
:
TAQUET
(Pawl).
We program segment 0 to " 1 " when we want to operate the pawls.
We program segment 0 to " 0 " in the reverse case.
• Par Address
5D
: best displayed in segment mode.
Segment
7
: Not used.
Segment
6
:
DPLX
(Multiplex).
We program segment 6 to " 1 " if we want to use a multiplex interconnected group.
We program segment 6 to " 0 " if we want the Series 32 to work in simplex.
Segment
5
: Not used.
Segment
4
: Not used.
Segment
3
:
NIVSIN
(Levels Damaged by Fire).
We program segment 3 to " 1 " if we want to control Levels Damaged by Fire.
We program segment 3 to " 0 " in the reverse case.
Segment
2
:
DSERVS
(Double Selective Service).
We program segment 2 to " 1 " if we want to operate 2 Service Selective.
We program segment 2 to " 0 " in the reverse case.
Segment
1
: Not used.
Segment
0
: Not used.
• Par Address
5E
:
TRAUN0
(Automatic Homing Time to Level 0) best displayed in
hexadecimal.
At this address, we program the time that runs between the moment when the apparatus is
being called and its automatic homing to level 0.
We can program a time from 1 to 15 minutes at intervals of 1 minute.
See page 94 for the conversion between decimal and hex, from 0 to 255 ....... 00 to FF.
By programming 00, this function will not be used.