Installation manual

Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 64
PARAMETER DEFINITIONS
Par Address
5B
:
TYPHYD
(Hydraulic Type)
best displayed in hexadecimal.
At this address, we program the type of hydraulic that the Series 32 will drive.
See in the list below the number which has been attributed to the main types of hydraulics
currently known:
0 = GMV-MARTINI 3 Valves.
0 = MORRIS.
0 = OMAR.
1 = HAMMOND-CHAMPNESS.
1 = ALGI.
2 = DOVER.
3 = BERINGER ELECTRONIQUE.
4 = Can be defined in addresses 38 to 3F.
Par Address
5C
: best displayed in segment mode.
Segment
7
: Not used.
Segment
6
:
RAMDES
(Down Collective).
We program segment 6 to " 1 " when we want to carry out the Down Collective.
We program segment 6 to " 0 " in the reverse case.
Segment
5
:
BASE 8N
(Base 8 Level).
We program segment 5 to " 1 " when we want to set up a single automatic operation or a 1
button collective up and down. All this up to level 8 just by using using the BG15 (without
addition of the BG18).
We program 5 to " 0 " in the reverse case.
Segment
4
: Not used.
Segment
3
:
DNH
(Oil Level Fault).
We program segment 3 to " 1 " when we want to operate the Oil Level Fault Contact.
We program segment 3 to " 0 " in the reverse case.
Segment
2
: Not used.
Segment
1
:
DEMDIR
(Direct Start-Up).
We program segment 1 to " 1 " when we want to carry out a direct start-up.
We program segment 1 to " 0 " when we want to carry out a Star-Delta start-up.