Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 61
PARAMETER DEFINITIONS
• Par Address
44
:
TIRP1
(Re-Open Door 1 Delay)
best displayed in hexadecimal.
At this address, we program the desired time delay between reversing the direction of the
door movement when re-opening .
This may be necessary if the inertia of the door is high.
Time is adjustable between 00ms and 2.55 seconds at intervals of 0.01 seconds.
See page 94 for the conversion between decimal and hex, 0 to 255 ....... 00 to FF.
• Par Address
45
:
TFR8
(Filtering of 8)
best displayed in hexadecimal.
At this address, we program the time allowed for contact bounce of the car gate switch
(input 8).
Time is adjustable between 00ms and 2.55 seconds. Values are entered at intervals of
10ms.
E.G.: If a time delay of 500ms is desired, this would correspond to 50 × 10 ms.
Consulting page 94, we can see that this equals 32 in hex, so the value programmed
would be 32.
• Par Address
46
:
TVP1/2
(Maximum time between 8 and 10) best displayed in hex.
At this address, we program the maximum time allowed between inputs 8 and 10 when a
call has been made.
E.G.: Flush shaft ascent fitted with swing landing doors and a mobile retiring ramp.
The safety chain circuit is such that when the lift does not move and all the doors are shut,
8 will appear. Making a call, combined with the fact that 8 is present, activates the mobile
retiring ramp. If all goes well, 10 will appear almost instantly. We will program a small
interlock time of 3 seconds. If, by contrast, the interlock is not done, once the time has
passed, the retiring ramp is de-activated to avoid it remaining under tension - permanently!
The timing is the same for doors 1 and 2.
We can program a value from 0 to 255 seconds.
See page 94 for the conversion between decimal and hex, 0 to 255 ....... 00 to FF.
• Par Address
47
:
TIGP01
(Door 1 Integrator Time) best displayed in hexadecimal.
At this address, we program the maximum time allowed for the door 1 integrator time in
seconds and hex.
See page 94 for the conversion between decimal and hex, 0 to 255 ....... 00 to FF.
If we program 00, there is no door integrator.