Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 59
PARAMETER DEFINITIONS
• Par Address
3C
: best displayed in segment mode.
Same address
38
for stage:
• Par Address
3D
: best displayed in segment mode.
Same address
38
for stage:
• Par Address
3E
: best displayed in segment mode.
Same address
38
for stage:
• Par Address
3F
: best displayed in segment mode.
Same address
38
for stage:
• Par Address
40
: best displayed in segment mode.
At this address, we program the mechanical characteristics of DOOR 1 which the Series
32 will operate.
Segment
7
:
RGPT
Segment
6
:
VERSTF1
(Door Forced when Closed).
We program segment 6 to " 1 " when we want to give a close signal in the case where a
movement is desired. A message is given stating that the closure limit switch of Door 1 is
open but that 8 from the safety chain has not been closed.
If there is a mechanical problem, in spite of 8 from the safety chain remaining closed, the
closure relay will be activated when the door integrator time has run out.
We program segment 6 to " 0 " in the reverse case.
Segment
5
:
P1SFCOU
(Door 1 without Opening).
We program segment 5 to " 1 " when we want to operate automatic door 1 without an
opening limit (FCOU).
Segment
4
:
P1SFCFE
(Door 1 without Closure Limit).
We program segment 4 to " 1 " when we want to operate automatic door 1 without a
closing limit (FCFE).
We program segment 4 to " 0 "when we want to operate an automatic door fitted with a
closing limit (FCFE).
Segment
3
:
PMAFCP1
(Door 1 Extended Close Time).
We program segment 3 to " 1 " to hold the door close signal an additional 300ms after the
closed limit has been reached.
We program segment 3 to " 0 " when we want to stop the movement from when door 1
reaches the close limit.