Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 58
PARAMETER DEFINITIONS
Segment
7
:
V4
(Valve 4).
Programming segment 7 to " 1 " activates valve N° 4 at this stage.
Programming segment 7 to " 0 "results in the reverse case.
Segment
6
:
V3
(Valve 3).
Programming segment 6 to " 1 " activates valve N° 3 at this stage.
Programming segment 6 to " 0 "results in the reverse case.
Segment
5
:
V2
(Valve 2).
Programming segment 5 to " 1 " activates valve N° 2 at this stage.
Programming segment 5 to " 0 "results in the reverse case.
Segment
4
:
V1
(Valve 1).
Programming segment 4 to " 1 " activates valve N° 4 at this stage.
Programming segment 4 to " 0 "results in the reverse case.
Segment
3
: Not used.
Segment
2
:
LINE
(Line Contactor).
Programming segment 2 to " 1 " activates the line contactor at this stage.
Programming segment 2 to " 0 "results in the reverse case.
Segment
1
:
DELTA
(Delta Contactor).
Programming segment 1 to " 1 " activates the delta contactor at this stage.
Programming segment 1 to " 0 "results in the reverse case.
Segment
0
:
STAR
(Star Contactor).
Programming segment 0 to " 1 " activates the STAR contactor at this stage.
Programming segment 0 to " 0 "results in the reverse case.
Par Address
39
: best displayed in segment mode.
Same address
38
for stage:
Par Address
3A
: best displayed in segment mode.
Same address
38
for stage:
Par Address
3B
: best displayed in segment mode.
Same address
38
for stage: