Installation manual

Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 54
PARAMETER DEFINITIONS
Par Address
1A
: best displayed in segment mode.
Segment
0
:
Programming of the Crossed Slow Speed Distance for in-
between levels 0 to 1.
We program segment 0 to " 1 " when the set up of the site is such that it is necessary to cross
the Slow Speed distance zones between levels 0 and 1.
We program segment 0 to " 0 " when the set up of the site does not impose into the Crossed
Slow Speed Distance between levels 0 and 1.
Segment 1: programming of the crossed slow speed distance for between levels 1 and 2.
Segment 2: programming of the crossed slow speed distance for between levels 2 and 3.
Segment 3: programming of the crossed slow speed distance for between levels 3 and 4.
Segment 4: programming of the crossed slow speed distance for between levels 4 and 5.
Segment 5: programming of the crossed slow speed distance for between levels 5 and 6.
Segment 6: programming of the crossed slow speed distance for between levels 6 and 7.
Segment 7: programming of the crossed slow speed distance for between levels 7 and 8.
Par Address
1B
: best displayed in segment mode.
Segment 0: programming of the crossed slow speed distance for between levels 8 and 9.
Segment 1: programming of the crossed slow speed distance for between levels 9 and 10.
Segment 2: programming of the crossed slow speed distance for between levels 10 and 11.
Segment 3: programming of the crossed slow speed distance for between levels 11 and 12.
Segment 4: programming of the crossed slow speed distance for between levels 12 and 13.
Segment 5: programming of the crossed slow speed distance for between levels 13 and 14.
Segment 6: programming of the crossed slow speed distance for between levels 14 and 15.
Segment 7: not used.
Par Address
1C
: Not used.
Par Address
1D
:
NUSPLX
(SimPLeX NUmber). best displayed in hexadecimal.
At this address, we program the simplex number in case of Multiplex.
As the number of apparatus that can be put into an interconnected group is 2, the simplex
number will go from 00 to 01.
Par Address
1E
:
TFR10
(Filtering of 10).
Best displayed in hex mode.
At this address, we program the time that runs between the moment where 10 of the safety
chain is good, and the moment when movement occurs.
This timing is to filter the mechanical jumps on 10 and can last up to 500 milliseconds.
This timing is programmable at intervals of 10ms and in hex.
See page 94 for the conversion between decimal and hex, from 00 to 255 ....... 00 to FF.