Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 53
PARAMETER DEFINITIONS
• Par Address
17
: best displayed in segment mode.
Segment
0
to
7
:
(Mask the Landing Calls for Down, from levels 8 to 15).
• Par Address
18
: Not used.
•
Par Address
19
: (Only with vanes) best displayed in segment mode.
Segment 7: not used.
Segment 6: not used.
Segment 5: not used.
Segment 4: not used.
Segment 3: not used.
Segment 2: not used.
Segment
1
:
PVCRH
(Slow Speed Distance crossed at Upper Level).
We program segment 1 to " 1 " when the set up of the site is such that it is necessary to
cross the Slow Speed Distance of the last upper in-between-level.
We program segment 1 to " 0 " when the set up of the site does not impose into the
Crossed Slow Speed Distance of the last upper in-between level.
Additionally, see the addresses 1A and 1B.
Segment
0
:
PVCRB
(Slow Speed Distance crossed at Lower Level).
We program segment 0 to " 1 " when the set up of the site is such that it is necessary to
cross the Slow Speed Distance Zones of the last lower in-between level.
We program segment 0 to " 0 " when the set up of the site does not impose into the
Crossed Slow Speed Distance of the last lower in-between level.
Additionally, see addresses 1A and 1B.
• Par Address
19
:
TPISO
(Only with a slotted tape) (Re-Levelling Timing).
Best displayed in hexadecimal mode.
At address 19, we program the maximum time for a re-levelling movement.
We can program a value from 2 to 10 seconds at intervals of 1 second.
If we program a value under 2 seconds, a 2 seconds value will be imposed.
If we program a value over 10 seconds, a 10 seconds value will be imposed.
See page 94 for the conversion between decimal and hex, from 0 to 255 ... 00 to FF.