Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VII - page 50
PARAMETER DEFINITIONS
Segment
3
:
OPTOM
(Fireman Service Option).
Programming segment 3 to " 1 " selects the fireman service option.
Programming segment 3 to " 0 " disables this option.
In this case, the Series 32 ignores the state of the fireman service input.
Segment
2
:
MHSPF
(Out of Service Door Closed).
Arriving at the Out of Service Level, the doors will open and close indefinitely until this
function is left.
Programming segment 2 to " 0 " results in the car parking with the door open, after the Out
of Service sign is shown.
Segment
1
and
0
:
TYPOMP
(Type of Fire man Service)
We program in these 2 segments the code of the type of fireman service required.
Call code of the different types of fireman service:
• Par Address
0A
:
TIG
(Time Integrator).
Best displayed in hex mode.
At this address, we program the integrator timing in seconds and in hex.
We can program a value from 02 to 45 seconds.
If we program a value under 2 seconds, a value of 02 seconds will be imposed (Norm).
If we program a value over 45 seconds, a value of 45 seconds will be imposed (Norm).
See page 94 for conversion between hex and decimal from 00 to 255 ....... 00 to FF.
• Par Address
0C
:
TPLU
(Automatic Light Timing).
Best displayed in hexadecimal mode.
At the address 0C, we program the timing of the automatic light in seconds and in hex.
We can program a value from 02 to 255 seconds.
See page 94 for conversion between decimal and hex, from 00 to 255 ....... 00 to FF.
ENGLISH FIRE SERVICE ...code 01.
SWISS FIRE SERVICE ...code 10.
FRENCH FIRE SERVICE ...code 00.