PARAMETER DEFINITIONS
To read and modify the parameters, it is necessary to put the little switch on the left
to the down position, called PAR.
Before the word ADDRESS, the little PAR switch must be down, and RAM must be
up. Now we can define the contents of the parameters. It is then necessary to put the little
switch down.
The small dot at the bottom to the right of the display is now lit.
Par Address
00
:
CDDEF
(Last Fault Code).
Best displayed in hexadecimal mode.
At this address, the Series 32 displays the code of the last fault.
Par Address
01
:
CADDEF
(Last but-one-fault code).
Best displayed in hexadecimal mode.
At this address, the Series 32 displays the last-but-one fault code.
Par Address
02
: Best displayed in segment mode.
Best displayed in hexadecimal mode.
At this address, the Series 32 displays the last-but-one fault code.
See the addresses 5D and 63 to change the values.
The segments of address N°2 cannot be changed directly!!!
Segment
7
:
REGUL
(Control System).
We program segment 7 to " 1 " if the Series 32 is to drive an independent speed control
system.
We program segment 7 to " 0 " in the reverse case.
Segment
6
:
DPLX
(DuPLeX).
We program segment 6 to " 1 " if the Series 32 is to be switched into a MULTIPLEX
battery.
We program segment 6 to " 0 " if the Series 32 is to work in SIMPLEX.
Segment
5
:
ISO
(Re-levelling).
We program segment 5 to " 1 " if the Series 32 is to drive the RE-LEVELLING option
(Open doors and Closed doors).
We program segment 5 to " 0 " in the reverse case.