EXPLANATION OF PARAMETERS (4/7).
• Address
00E
:
Opt
, Option.
Segment
7
:
ML220V
, MLIft 220V.
00E Opt
10000000
Segment 7 is programmed ON when the Vector drive is on a three phase 220V
network.
Segment 7 is programmed OFF when the Vector drive is on a three phase 400V
network.
Segment
6
:
D65°
, Fault T°>65°.
00E Opt
01000000
Segment 6 is programmed ON to increase the radiator temperature detection threshold
from 60°C to 65°C.
Segment 6 is programmed OFF to keep the detection threshold at 60°C.
Segment
5
:
APPDIR
, Direct Approach.
00E Opt
00100000
Segment 5 is programmed ON to remove V0 so that the car can level with direct
approach.
Segment 5 is programmed OFF if this is not desired.
Segment
4
:
RETSEC
, Delay on safety contactor.
00E Opt
00010000
Segment 4 is programmed ON to filter the rebound of the S contactor contacts on start-
up, and when these contacts are used to cut the motor power supply.
Segment 4 is programmed OFF when the S contacts are not used to control the motor.
Segment
3
:
MLI
, V.F. + « NON AUTINOR » Controller.
00E Opt
00001000
Segment 3 is programmed ON when the B32 is associated to an other controller than
AUTINOR.
Segment 3 is programmed OFF when the B32 is associated to an AUTINOR controller
using the slotted tape.
Segment
2
:
BATERI
, Battery.
00E Opt
00000100
Option available later in 1999
Segment 2 is programmed ON to activate the emergency return to floor level using battery
power supply. This option requires an extra, emergency power supply.
Segment
1
:
NOBAND
, No slotted tape.
00E Opt
00000010
Segment 1 is programmed ON when there is no tape or O03 tape-head. In this case, a
high speed tachometer is required.
Segment 1 is programmed OFF when the speed information cames from the slotted
tape and O03 tape-head.