ELECTROMAGNETIC COMPATIBILITY PRECAUTIONS (2/4)
At not time should the screening cable replace the yellow-green earthing cable.
ADVICE: In order to ensure the electromagnetic compatibility, it may be necessary to use to connect to the
motor, a metal stuffing box with a screening contact allowing an efficient electrical link between the
flat screening cable and the metal housing (see figure below).
If the motor terminal box is isolated, then a metal stuff box is of course useless. The screening cable
should be linked in the shortest way to the motor earth terminal block.
3. The other links between the MB32 Vector drive and the motor, i.e. .the brake (+BR and
-BR), the motor thermistor (0V, STH) can run together but kept at least 10 cm from the
power cables.
EXAMPLE:
Conventional connection :
Controller:
Phase
Screened cable
cables
Yellow/Green
earthing cable
TO INSERT THE SCREENING CABLE
LOWER THE MOBILE PLATE
USING A SCREWDRIVER
Screening cable
11 12 13PE
Motor:
W2 U2
V2
U1
V1
W1
Screening flat cable
linked in the shortest way
to the earth terminal
Phase cables
Screened cable
earthing cable
Yellow/Green
Terminal box
Motor earth
terminal
Note: Keep the motor cable as far apart from the power cable
as possible, inside as well as outside the controller.
Note: The cables should only be separated from the screening
once inside the terminal box.
Connection using stuff-box :
CURVED SEAL
FLAT SEAL
FLAT CABLE
TUBING
BOX WALL
TERMINAL
SCREENING
10 cm min
SHAFT WIRING
HANGING CABLE
L1, L2, L3 + EARTH
L1, NEUTRAL
CONTROLLER
M
MOTOR SCREENED CABLE
11,12,13 AND EARTH + SCREENING
MOTOR THERMISTOR
BRAKE
POWER
SUPPLY
ARRIVAL BOX
MOTOR
SCREENED
CABLE
ONLY
THERMISTOR,
BRAKE,
ENCODER,
TRUNKING
10 cm min
INCREMENTAL
Check that the power supply arrival does not flow close
to the MB32 Vector drive and motor link.