Installation manual
Série 32 Mlift Vector - Prog.Vectorielle Installation manual Chapter VI - page 22
VVVF DOOR DRIVE OP15 2/2
(*) For the Slow limit contacts, 2 choices:
A Slow down limit on opening
which is connected to
K5
on
0V
[1] and
CB
[4].
A Slow down limit on closing
which is connected to
K5
on
0V
[1] and
CA
[3].
And a relay which give the re-opening
, to
K3
between [1] and [2].
The box give equally 1 contact (NO) available on the terminal
K3
.
Programme:
OP15
R
xx
OR
An Incremental Encoder
mounted on the door motor which is connected to
K5
on
0V
[1],
16V
[2],
CA
[3] and
CB
[4].
The OP15 deliver to the controller a simulation of the:
•
OPening End Limit contact
(
ELOP
[FCOU]) between [1] and [2] to the
K3
terminal,
•
And CLosing End Limit contact
(
ELCL
[FCFE)) between [3] and [4] to the
K3
terminal.
Programme:
OP15
I
xx
NOTE: The VVVF / Motor link should be made with a SCREEN CABLE and as short as
possible.
(The screen cable is not delivered but available as a spare part [ref AUTINOR: 3444])
IMPERATIVE
Separate the conductors carrying large current and those carrying
electric information at low current.
For more information refer you at the documentation [ref AUTINOR: ????)