Operating instructions
Vector Control Chassis Type Frequency Converter Parameterizing steps
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 9-31
Parameter assignments depending on setpoint source (P368) and control type (P100):
P368 = Setpoint source
Parameter description
P368 = 0
PMU +
MOP
P368 = 1
Analog inp.
+ terminals
P368 = 2
FSetp +
terminals
P368 = 3
MOP +
terminals
P368 = 4
USS
P368 = 7
OP1S +
FSetp
P554.1 Src ON/OFF1 B0005 B0022 B0022 B0022 B2100 B2100
P555.1 Src OFF2 1 B0020 B0020 B0020 B2101 1
P561.1 Src InvRelease 1 B0016 1 1 1 1
P565.1 Src1 Fault Reset B2107 B2107 B2107 B2107 B2107 B2107
P567.1 Src3 Fault Reset 0 B0018 B0018 B0018 0 0
P568.1 Src Jog Bit0 0 0 0 0 B2108 B2108
P571.1 Src FWD Speed 1 1 1 1 B2111 B2111
P572.1 Src REV Speed 1 1 1 1 B2112 B2112
P573.1 Src MOP Up B0008 0 0 B0014 0 0
P574.1 Src MOP Down B0009 0 0 B0016 0 0
P580.1 Src FixSetp Bit0 0 0 B0014 0 0 0
P581.1 Src FixSetp Bit1 0 0 B0016 0 0 0
P590 Src BICO DSet 0 0 0 0 0 0
P651.1 Src DigOut1 B0107 B0107 B0107 B0107 B0107 B0107
P652.1 Src DigOut2 B0104 B0104 B0104 B0104 B0104 B0104
P653.1 Src DigOut3 0 B0115 0 0 0 0
P654.1 Src DigOut4 0 0 0 0 0 0
Setpoint conn. parameter KK0058 K0011 KK0040 KK0058 K2002 KK0040
v/f characteristic + n/f-control: Setpoint connector parameter (Setp-KP) = P443
T-control + n/f control: Setpoint connector parameter (Setp-KP) = P486
P100 = control type
Parameter description P100 = 0
V/f + n
P100 = 1
V/f
P100 = 2
Textile
f-Reg.
(P587 = 0)
n-Reg.
(P587 = 0)
P100 = 5
T-Reg.
P038.1 DispTorqConn.r39.1 - - - - - Sw-KP
P038.1 DispTorqConn.r39.2 - - - - - K0165
P040.1 DispSpdConn.r41.1 Setp CP Setp CP Setp CP Setp CP Setp CP KK0150
P040.2 DispSpdConn.r41.2 KK0148 KK0148 KK0148 KK0148 KK0148 KK0148
P040.3 Disp Freq Conn.r41.3 - - - KK0091 KK0091 KK0091
P042.1 Disp Freq Conn.r43.1 Setp CP Setp CP Setp CP Setp CP Setp CP KK0150
P042.2 Disp Freq Conn.r43.2 KK0148 KK0148 KK0148 KK0148 KK0148 KK0148
P042.3 Disp Freq Conn.r43.3 KK0199 KK0199 KK0199 KK0091 KK0091 KK0091
Bxxxx = Binector (Digital signal; values 0 and 1)
Kxxxx = Connector (16-bit signal; 4000h = 100 %)
KKxxxx = Double connector (32-bit signal; 4000 0000h = 100 %)