Operating instructions
Vector Control Chassis Type Frequency Converter Parameterizing steps
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 9-9
Successful parameterization of the units by download is only ensured if
the unit is in the "Download" status when the data is being transferred.
Transition into this status is achieved by selecting the "Download"
menu in P060.
P060 is automatically set to 6 after the download function has been
activated in the OP1S or in the SIMOVIS service program.
If the CUVC of a converter is replaced, the power section definition has
to be carried out before parameter files are downloaded.
If only parts of the entire parameter list are transferred by download, the
parameters of the following table must always be transferred too, as
these automatically result during the drive setting from the input of other
parameters. During download, however, this automatic adjustment is
not carried out.
Parameter number Parameter name
P109 Pole pair number
P352 Reference frequency = P353 x P109 / 60
P353 Reference frequency = P352 x 60 / P109
Table 9-4 Parameters which always have to be loaded during download
If parameter P115 = 1 is described during download, the automatic
parameterization is then carried out (according to the setting of
parameter P114). In the automatic parameterization, the controller
settings are calculated from the data of the motor rating plate.
If the following parameters are described during download, they are not
then re-calculated by the automatic parameterization:
P116, P128, P215, P216, P217, P223, P235, P236, P240, P259, P278,
P279, P287, P295, P303, P313, P396, P471, P525, P602, P603.
NOTE