Operating instructions

Parameterization Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
8-2 Operating Instructions SIMOVERT MASTERDRIVES
X300
ON key
OFF key
Lower key
Toggle key
Raise key
Reversing key
Seven-segment display for:
Drive statuses
Alarms and
faults
Parameter numbers
Parameter indices
Parameter values
Fig. 8-1 PMU parameterizing unit
Key Significance Function
ON key For energizing the drive (enabling motor activation).
If there is a fault: For returning to fault display
OFF key For de-energizing the drive by means of OFF1, OFF2 or OFF3
(P554 to 560) depending on parameterization.
Reversing key
For reversing the direction of rotation of the drive.
The function must be enabled by P571 and P572
Toggle key For switching between parameter number, parameter index
and parameter value in the sequence indicated (command
becomes effective when the key is released).
If fault display is active: For acknowledging the fault
Raise key For increasing the displayed value:
Short press = single-step increase
Long press = rapid increase
Lower key For lowering the displayed value:
Short press = single-step decrease
Long press = rapid decrease
Hold toggle key
and depress raise
key
If parameter number level is active: For jumping back and forth
between the last selected parameter number and the
operating display (r000)
If fault display is active: For switching over to parameter
number level
If parameter value level is active: For shifting the displayed
value one digit to the right if parameter value cannot be
displayed with 4 figures (left-hand figure flashes if there are
any further invisible figures to the left)
Hold toggle key
and depress lower
key
If parameter number level is active: For jumping directly to the
operating display (r000)
If parameter value level is active: For shifting the displayed
value one digit to the left if parameter value cannot be
displayed with 4 figures (right-hand figure flashes if there are
any further invisible figures to the right)
Table 8-1 Operator control elements on the PMU