Operating instructions
Vector Control Chassis Type Frequency Converter Faults and Alarms
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 11-11
Fault
number
Fault Counter-measure
F080 TB/CB Init.
Error during initialization of the board at the
DPR interface
r949 = 1: TB/CB not inserted or TB/CB board
code incorrect
r949 = 2 TB not compatible
r949 = 3: CB not compatible
r949 = 5: Error in initialization data
r949 = 6: Timeout during initialization
r949 = 7: TB/CB board double
r949 = 10: Error in configuration channel
Check that the T300 / CB board is inserted
correctly
Check the CB initialization parameter:
• P918 CB Bus Address
• P711 to P721 CB parameters 1 to 11
F081 Opt. Board Heartb
TB, CB or SCB no longer processes the
monitoring counter
r949 = 0: TB/CB Heartbeat counter
r949 = 1: SCB Heartbeat counter
• Replace SCB, TB or CB
• Check connection between subrack and
optional boards
F082 TB/CB Tlg
No new process data have been received by
the TB or the CB within the telegram failure
time.
r949 = 1: TB/CB
r949 = 2: 2. CB
• Check the connections of the CB/TB.
• Check P722 “CB/TB TLG OFF“.
• Replace CB or TB.
F087 SIMOLINK initialization fault • Replace CU
• Replace SLB
F090 MId Param.
An error occurred when attempting to change
a parameter from the standstill measurement
or the rotating measurement (Mot ID).
Power down and power up again. If it re-
occurs, replace the CU.
F091 MId Time
The rotating measurement takes longer than
programmed in a measured status. Possible
causes:
• Load torque too high
• Load torque not uniform
• Ramp-function generator disabled
Eliminate the cause and re-start the
measurement (power up the converter again).
If it re-occurs, replace the CU.